SMC Automation and Manufacturing Skills (AIMS) Certification - Certified Automation Technician Level III Exam Prep
Free practice questions

Free AIMS Practice Questions

10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.

Start the free practice test → ★★★★★4.9/5 from 2,400+ candidates · No signup

These 10 free AIMS questions are organized by exam domain, so you can see how each part of the SMC Automation and Manufacturing Skills (AIMS) Certification - Certified Automation Technician Level III blueprint is tested. Reveal the answer and explanation under each question.

Domain 1: Programmable Controllers II

Question 1

A machine builder supplies a set of PNP (sourcing) proximity sensors for a new station. For these sensors to operate correctly, each PLC discrete input point must:

Show answer & explanation

Correct answer: B - Sink current from each sensor, requiring sinking input points

Question 2

A retentive on-delay timer with a 10-second preset has accumulated 6 seconds when its rung condition goes false. Thirty seconds later the rung becomes true again. No reset instruction has executed. The timer's done bit will set after an additional:

Show answer & explanation

Correct answer: C - 4 seconds

Question 3

A stop pushbutton with a physically normally-closed contact is wired to a PLC input as part of a motor start circuit. In the ladder program, the stop function should be programmed as:

Show answer & explanation

Correct answer: B - A normally-open instruction, since the input is true when unpressed

Domain 2: Human Machine Interface

Question 4

A momentary pushbutton object on an HMI touchscreen may serve as a machine's emergency stop device, provided the HMI communicates with a safety-rated controller.

Show answer & explanation

Correct answer: B - False

Question 5

An HMI momentary pushbutton jogs a conveyor. During a network interruption while the operator was holding the button, the conveyor continued to run after the button was released. The MOST appropriate corrective action is to:

Show answer & explanation

Correct answer: C - Add a PLC-side communication watchdog that clears HMI-written bits on loss

Domain 3: Applied Automation

Question 6

A double-acting cylinder has a 63 mm bore and a 20 mm rod, operating at 6 bar. The theoretical RETRACT force is approximately:

Show answer & explanation

Correct answer: B - 1,682 N

Question 7

An inductive proximity sensor with a nominal sensing distance of 8 mm, rated for a mild steel target, is installed to detect an aluminium target across a 6 mm gap. The MOST likely result is:

Show answer & explanation

Correct answer: A - Intermittent or no detection, as non-ferrous targets reduce sensing range

Domain 4: Applied Troubleshooting

Question 8

A double-acting cylinder extends at normal speed but retracts noticeably slowly. Supply pressure is correct at the station, the retract solenoid is confirmed energised, and neither flow control has been adjusted since commissioning. What should be checked NEXT?

Show answer & explanation

Correct answer: C - A restricted exhaust silencer on the directional control valve

Question 9

A VFD driving a loaded conveyor trips on a DC bus overvoltage fault every time the conveyor is commanded to stop. It runs without fault at constant speed. The MOST appropriate corrective action is to:

Show answer & explanation

Correct answer: D - Extend the deceleration time or fit a dynamic braking resistor

More AIMS practice questions

Question 10

A three-phase motor is supplied from a 480 V wye-connected system. The voltage measured between any one phase conductor and the system neutral is approximately:

Show answer & explanation

Correct answer: A - 277 V

That's 10 of 1,030

The full bank has 1,020 more AIMS questions with explanations.